Air temperature and humidity in the data center are controlled permanently
and reported to a superordinate monitoring system. A high-precision air
conditioning system by Liebert HIROSS keeps the temperature constant
electronically at a value that is optimal for the servers. Continuous control
and, if necessary, adaptation of air temperature grant protection against
excessive thermal strain on the hardware in the racks.
Climate Control
Power-saving, indirect outdoor cooling system
Redundancy cooler (water chiller) with 3 x 120
kW in n + 1-redundancy with
automatic switchover
Redundancy pumping system for cooler
Redundancy internal recirculating air cooling units with 2 x 73,5
kW temperature-sensitive cooling
capacity in n + n-redundancy (100 %), (extensible)
Master/slave control for the internal recirculating air cooling
units
Supply of cooling air via a double layer floor
Layout of trade-name racks by Knürr according to the cool-warm-corridor
principle for server blades and other high packing densities
Air temperature 21 °C ± 2 °C
Air filtering of return air for abrasive particles and respirable
dust according to VDI
2054-guide line with filter category G4