The relevant rooms of the data center are equipped with modular security walls,
IT standard-conforming
one-door systems, suspended ceilings and double floors. All supply
engineering components are situated in separate areas of the building.
Building
Easily accessible by car via autobahn
A1,
A2,
A40/B1,
A43 and
A45
Unobtrusive location at TechnologieParkDortmund
Parking area for customers on the company compound
Isolated, three-story building
Fire protection walls and fire protection doors in F90+ and T90
quality rating, respectively, in data center and engineering room according
to DIN
4102-2-rule/F90 including legal building inspection authorization
Comprehensive grounding grid and lightning protection
Data center area of approximately 90 square meters including
engineering area
472,5 kW connected load,
extensible up to 600 kW
240 kW climatisation power,
extensible up to 360 kW with
n+1-redundancy
Complete access protection for standby power supply system and water
chiller
Separated by open ground of server rooms, engineering room and
installation room
Warning system for water with sensor loop and monitoring of sensor
breakage, for monitoring of liquid leakage and indication of leakage sector
for data center and engineering room by BARTEC
Highly sensitive early fire detection system
VESDA by
LaserFOCUS (Smoke intake system) with programmable sensitivity for data
center and engineering room
Automatic fire detection system including central fire alarm system
according to guide line of
VdS
Nitrogen extinguishing system with steel storage cylinders
conforming to
VdS